Extinction Centrals

Reference
FOC-618 Model: PH.PL.FIP.R8



8 zones and 8 relays conventional fire alarm & extinguishing panel. 1 Extinguishing area with 8 zones. Up to a maximum of 8 keypads units per system. Built in communicator supporting Contact I.D protocol. Power supply 27.6 VDC, 2A



Features
- Alarm and extinguishing panel , 8 zones and 8 relay for conventional systems
- 1 extinguishing area with 8 zones (mode 2)
- LCD keyboard for para supervision, control and system programming
- Up to 8 keyboards per system
- 2 supervised siren outputs
- 1 non supervised output of general failure
- Up to 1.000 log events
- Up to 16 fully supervised power units (PSUs) can be connected to expansion modules,
- It incorporates communicator with support of protocol Contact ID
- Automatic detection of modules when installing (relay, zones and keypad modules)
- Bypasses for zone inputs and relay outputs
- Intellizone operation (alarm verification)
- Day / Night operation that reduces false alarms during specific hours of the day using the intellizone function (used for example in smoking areas during working hours)
- The system can use emergency pushbuttons or a key combination on keyboards and / or extinguishing zones to activate the global evacuation condition
- Walk Test (WalkTest)
- RS232 serial connection
- Operating temperature -5 ° C ~ + 40 ° C
- Power supply: 27.6V DC / 2A
- Auxiliary output: 24V DC (± 10%), 800 mA
- Batteries: Up to 2 12V / 7Ah batteries
- Dimensions: 450 x 310 x 90 mm
- Certificate according to European directives ΕΝ 54-2: 1997 / Α1: 2006 / AC: 1999, ΕΝ 54-4: 1997 / Α2: 2006 / AC: 1999 and ΕΝ 12094-1: 2003 (extinction) and EC certificate of conformity

Notes




Share to your social networks.      